Skip to main content
Schneider Electric LP1K120045BD3 — Contactors

Schneider Electric LP1K120045BD3 TeSys K Contactor, 20A AC-1

MPNLP1K120045BD3
Active

Schneider Electric TeSys K contactor, LP1K120045BD3, 4P (4 NO), AC-1, ≤440 V, 20 A, 24 V DC coil.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LP1K120045BD3 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load

Ratings & Performance

LP1K120045BD3 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz
Utilisation categoryAC-1

Contacts & Poles

LP1K120045BD3 — Contacts & Poles
ParameterValue
Pole configuration4P

Environmental

LP1K120045BD3 — Environmental
ParameterValue
Operating altitude2000 m without derating
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102

Approvals

LP1K120045BD3 — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1

Mechanical

LP1K120045BD3 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric LP1K120045BD3 is a TeSys K contactor with four normally-open power poles, rated for 20 A in AC-1 utilisation category (resistive loads) at up to 690 V AC 50/60 Hz. The coil is 24 V DC with a built-in bidirectional peak-limiting diode suppressor, so no external flyback diode is needed on the control side — that saves a component and a wiring step on the panel. AC-1 duty means it's designed for switching resistive loads — heaters, ovens, lighting banks — where the current and voltage are nearly in phase. The conventional free-air thermal current (Ith) is also 20 A at 50 °C, so the contactor is thermally rated for that current in open air.

The LP1K120045BD3 mounts on printed circuit boards — not a DIN-rail footprint. That makes it a good fit for custom control boards, OEM machine controllers, or panel designs where the contactor is soldered or bolted directly to a PCB rather than snapped onto a rail. The four NO poles give you independent switching of up to four separate resistive load circuits, or you can parallel them for higher current on a single load — though the AC-1 rating per pole stays 20 A. The contactor is rated for 3600 operations per hour and 10 million mechanical cycles, so it's built for continuous-duty applications like packaging lines or conveyor heating zones.

The LP1K120045BD3 carries approvals to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, and JIS C8201-4-1. That covers the major global markets — North America, Europe, China, Japan — so it's accepted in export machinery and multi-region installations. The rated insulation voltage (Ui) is 690 V per IEC 60947-4-1 and 600 V per UL 508 / CSA C22.2 No 14, and the rated impulse withstand voltage (Uimp) is 8 kV, which is standard for overvoltage category III environments.

Frequently asked questions

What is the closest alternative to the LP1K120045BD3 in the same family?

The closest peer is another TeSys K 4-pole contactor with the same AC-1 current rating but a different coil voltage — for example, the LP1K120045BD3 uses a 24 V DC coil; a variant with a 48 V DC or 110 V AC coil would be the same mechanical platform, same pole configuration, same mounting. The choice comes down to what control voltage your PLC or relay output provides.

What compliance documentation is available for the LP1K120045BD3?

The contactor is certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, and JIS C8201-4-1. The manufacturer provides a declaration of conformity and the UL/CSA listing marks on the nameplate. RoHS and REACH compliance is standard for Schneider TeSys K products, though the specific statement should be confirmed from the product certificate.

What are the key ratings of the LP1K120045BD3?

Rated operational current (Ie) is 20 A in AC-1 at 690 V (16 A derated above 70 °C). Conventional free-air thermal current (Ith) is 20 A at 50 °C. Rated operational voltage (Ue) is 690 V AC 50/60 Hz. Coil voltage is 24 V DC. Mechanical durability is 10 million cycles. Maximum operating rate is 3600 cycles per hour.

MPN