The LP1K12107MD clips onto a 35 mm DIN rail and occupies 45 mm width × 58 mm height × 57 mm depth. The 57 mm depth leaves clearance behind a 60 mm deep enclosure backplate — no up-tower swaps needed if the gland plate is already wired.
Schneider Electric LP1K12107MD TeSys K Contactor, 12A AC-3,
Schneider Electric TeSys K LP1K12107MD, 3-pole contactor, 12 A AC-3 at ≤440 V, 220 V DC coil, 1 NO auxiliary contact.
Specifications
| Parameter | Value |
|---|---|
| Product / component type | Contactor |
| Series / range | TeSys |
| Parameter | Value |
|---|---|
| Utilisation category | AC-3 AC-4 AC-1 |
| Parameter | Value |
|---|---|
| Pole configuration | 3P |
| Parameter | Value |
|---|---|
| Flame retardance | V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102 |
| Parameter | Value |
|---|---|
| Width | 45 mm |
| Height | 58 mm |
| Depth | 57 mm |
| Parameter | Value |
|---|---|
| Range of product | TeSys K |
| Device short name | LP1K |
| Inrush power in | 3 W (at 20 °C) |
| Compatibility code | LP1K |
| Pole contact composition | 3 NO |
| Hold-in power consumption in | 3 W at 20 °C |
| [Ie] rated operational current | 20 A (at 12 A at 16 A (at 10 MOhm for signalling circuit |
Product details
Frequently asked questions
What are the key ratings for this contactor?
Rated operational current is 12 A in AC-3 at ≤440 V, with a 220 V DC coil drawing 3 W. It covers AC-1, AC-3, and AC-4 utilisation categories. Flame retardance meets UL 94 V1.
What compliance documentation is available for the LP1K12107MD?
The contactor carries UL 94 V1 flame retardance certification and NF F 16-101/102 compliance for fire-smoke-toxicity in rail applications. Standard Schneider Electric declarations for RoHS, REACH, and CE are available through the manufacturer's documentation portal.