Skip to main content
Schneider Electric LP2K1201CD — Contactors

Schneider Electric LP2K1201CD TeSys K Reversing Contactor, 1

MPNLP2K1201CD
Obsolete

Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 12 A, 1 NC, 36 V DC coil, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LP2K1201CD — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control Resistive load
LP2K1201CD — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-4 AC-3 AC-1
LP2K1201CD — Contacts & Poles
ParameterValue
Pole configuration3P
LP2K1201CD — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP2K1201CD — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The 36 V DC coil suits control circuits common in panel installations. Rated for AC-1 (resistive), AC-3 (motor start/run), and AC-4 (plugging/inching) utilisation categories, so it covers both standard motor reversing and more demanding stop-start cycles. Altitude derating kicks in above 2000 m. Mechanical robustness is specified per IEC 60068-2-27: 15 Gn shock on Z axis when closed, 10 Gn when open — enough for most industrial environments but not extreme mobile applications.

If you need a drop-in replacement, a parametric cross-reference within the TeSys K family is possible, but pin compatibility and mounting footprint must be verified against your existing panel layout.

Spring-cage terminals accept 0.2–2.5 mm² solid or ferruled stranded; strip length of 8 mm avoids whiskers under the cage. The IP20 enclosure means no additional finger-duct clearance needed inside the panel. Flame retardance meets UL 94 V1 and NF F 16-101/102, so it passes rail and industrial fire-safety requirements. Protective treatment conforms to IEC 60068 and DIN 50016 for humidity and corrosion resistance — relevant if the panel sees condensation cycles.

Frequently asked questions

What are the key ratings for this reversing contactor?

AC-3 ≤440 V at 12 A for motor reversing, with a 36 V DC coil. It also covers AC-1 resistive loads and AC-4 plugging duty. The IP20 enclosure is rated for panel mounting only.

What compliance documentation is available for the LP2K1201CD?

The part carries UL 94 V1 flame retardance and conforms to NF F 16-101/102 for fire safety. Protective treatment meets IEC 60068 and DIN 50016. Standard RoHS/REACH declarations should be available from the manufacturer's documentation archive.