Skip to main content
Schneider Electric LP2K1201LD — Contactors

Schneider TeSys K LP2K1201LD Reversing Contactor, 3P, AC-3 1

MPNLP2K1201LD
Active

Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 12 A, 1 NC auxiliary, 200 V DC coil, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LP2K1201LD — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control Resistive load
LP2K1201LD — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4 AC-1
LP2K1201LD — Contacts & Poles
ParameterValue
Pole configuration3P
LP2K1201LD — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP2K1201LD — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The coil pulls in on 200 V DC, and there's one NC auxiliary contact built in for status feedback or a holding circuit.

The AC-3 rating is the one that matters for motor starting — 12 A at 440 V means it'll switch a 5.5 kW motor (roughly 7.5 HP) on a 400 V line without welding the contacts. AC-4 covers inching and plugging if you need it. The 690 V max operational voltage gives headroom for 480 V or 600 V systems, but the AC-3 current drops above 440 V — check the derating curve if you're running at 600 V. The 200 V DC coil is less common than 24 V or 110 V; make sure your control transformer or DC supply is set for that voltage before you spec it in.

It's a DIN-rail-mount contactor, 57 mm deep by 90 mm wide by 58 mm tall — fits a standard TS35 rail. The preassembled reversing busbar saves you the headache of cross-wiring two contactors and a mechanical interlock; just land your line and load wires. Ambient range is -25 to 50 °C, so it's fine in a ventilated enclosure on the floor.

Frequently asked questions

What are the key ratings I need to know for fit?

Three-pole reversing contactor, AC-3 rated 12 A at ≤440 V, coil is 200 V DC, one NC auxiliary contact. Dimensions are 57 mm deep, 90 mm wide, 58 mm tall.

What compliance documentation does this part carry?

It has IP20 protection per VDE 0106, flame retardance V1 per UL 94, and protective treatment per IEC 60068 and DIN 50016. The utilisation categories (AC-3, AC-4, AC-1) are per IEC standards.

Where is this contactor used?

It's for motor control and resistive load switching in control panels — specifically reversing applications where you need to change motor direction, like conveyors, small hoists, or pump stations.

MPN