Its AC-3 rating of 12 A at 440 V means it handles the inrush of a standard three-phase induction motor up to that current; the AC-1 rating covers resistive loads at the same current level. The 110 V DC coil is the control voltage you need to supply from your PLC or relay output.
The 110 V DC coil draws a holding current that your control transformer or power supply must deliver; verify the coil inrush is within your output card's rating. The flame retardance meets UL 94 V1 and NF F 16-101/102, which is standard for rail and industrial panel applications.
The contactor withstands 15 Gn shock on the Z axis when closed, and 10 Gn when open — sufficient for most industrial vibration environments. Operating altitude is 2000 m without derating.