Skip to main content
Schneider Electric LP2K1210FD3 — Contactors

Schneider TeSys K LP2K1210FD3 Reversing Contactor, 12 A AC-3

MPNLP2K1210FD3
Obsolete

Schneider Electric TeSys K reversing contactor, 3P, AC-3 12 A at 440 V, 110 V DC coil, 1 NO auxiliary, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LP2K1210FD3 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control Resistive load
LP2K1210FD3 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-1 AC-3 AC-4
LP2K1210FD3 — Contacts & Poles
ParameterValue
Pole configuration3P
LP2K1210FD3 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP2K1210FD3 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

Its AC-3 rating of 12 A at 440 V means it handles the inrush of a standard three-phase induction motor up to that current; the AC-1 rating covers resistive loads at the same current level. The 110 V DC coil is the control voltage you need to supply from your PLC or relay output.

The 110 V DC coil draws a holding current that your control transformer or power supply must deliver; verify the coil inrush is within your output card's rating. The flame retardance meets UL 94 V1 and NF F 16-101/102, which is standard for rail and industrial panel applications.

The contactor withstands 15 Gn shock on the Z axis when closed, and 10 Gn when open — sufficient for most industrial vibration environments. Operating altitude is 2000 m without derating.

Frequently asked questions

What are the key ratings of the LP2K1210FD3?

It is a 3-pole reversing contactor rated AC-3 12 A at 440 V, with a 110 V DC coil and one normally open auxiliary contact. It is preassembled with a reversing power busbar.

What is the IP rating of the LP2K1210FD3?

IP20 per VDE 0106, meaning finger-safe for panel installation but not protected against water ingress.

What compliance certifications does the LP2K1210FD3 carry?

Flame retardance is UL 94 V1 and NF F 16-101/102 compliant. Protective treatment meets IEC 60068 and DIN 50016. No RoHS or REACH statements are in the available records.

MPN
LP2K1210FD3