Skip to main content
Schneider Electric LV481004

Schneider Electric LV481004

MPNLV481004
Active

Residual current monitoring relay, VigiPacT RMH, 30mA-30A, 220/240VAC 50/60Hz, front panel mounting

$1,085.22 – $1,524.15Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LV481004 key specifications
ParameterValue
Type of settingKeypad Modbus address
Type of measurementEarth fault current internal measurement, range: 20...200 %, accuracy: +/- 20 %
Product or component typeMonitoring relay
Residual earth-leakage sensitity adjustment typeAdjustable
Supply voltage220...240 V AC 50/60 Hz 70...110 %
[Uimp] rated impulse withstand voltage8 kV
Current sensors compatibilityVigiPacT TOA earth leakage current sensor VigiPacT A earth leakage current sensor VigiPacT L earth leakage current sensor VigiPacT RM12T multiplexer
[Ithe] conventional enclosed thermal current8 A
Power consumption in8 VA
IK degree of protectionIK07 conforming to EN 50102
IP degree of protectionIP40 on front face: conforming to EN/IEC 60529 IP30 on side parts: conforming to EN/IEC 60529 IP20 on connection terminals: conforming to EN/IEC 60529
Communication serviceModbus slave

All specifications

LV481004 additional specifications
ParameterValue
Mounting supportFront panel
Wire stripping lengthAlarm circuit: 6 mm Multiplexer connection: 6 mm Pre alarm: 6 mm Voltage presence: 6 mm Power supply: 6 mm
Connections - terminalsAlarm circuit: terminal block cable(s) 0.2...2.5 mm² flexible AWG 22...AWG 12 Alarm circuit: terminal block cable(s) 0.2...2.5 mm² rigid AWG 22...AWG 12 Multiplexer connection: terminal block cable(s) 0.2...2.5 mm² flexible AWG 22...AWG 12 Multiplexer connection: terminal block cable(s) 0.2...2.5 mm² rigid AWG 22...AWG 12 Pre alarm: terminal block cable(s) 0.2...2.5 mm² flexible AWG 22...AWG 12 Pre alarm: terminal block cable(s) 0.2...2.5 mm² rigid AWG 22...AWG 12 Voltage presence: terminal block cable(s) 0.2...2.5 mm² flexible AWG 22...AWG 12 Voltage presence: terminal block cable(s) 0.2...2.5 mm² rigid AWG 22...AWG 12 Power supply: terminal block cable(s) 0.2...2.5 mm² flexible AWG 22...AWG 12 Power supply: terminal block cable(s) 0.2...2.5 mm² rigid AWG 22...AWG 12
Pollution degree3 conforming to IEC 60664-1
Relative humidity95 % at 55 °C
Electrical shock protection classClass II
Depth117 mm
Width72 mm
Height72 mm
Cut-out dimensions68 x 68 mm
StandardsEN/IEC 60947-2 Annex M EN/IEC 60755
RangeVigiPacT
Minimum load10 mA at 12 V
Refresh time0.5 s
Test functionLocal Remote test (via communication)
Earthing systemTN-S IT TT
Device short nameRMH
Relay applicationMonitoring relay
Threshold setting0.015...1 A adjustable in step of 0.001 A pre-alarm 1...30 A adjustable in step of 0.1 A pre-alarm 0.03...1 A adjustable in step of 0.001 A alarm 1...30 A adjustable in step of 0.1 A alarm
Tightening torqueAlarm circuit: 0.5 N.m Multiplexer connection: 0.5 N.m Pre alarm: 0.5 N.m Voltage presence: 0.5 N.m Power supply: 0.5 N.m
Overvoltage categoryIV
Mechanical robustnessFire resistance conforming to IEC 60695-2-1 IK protection 2 joules: IK07 conforming to EN 50102 Vibrations 13.2...100 Hz: 0.7 g Vibrations 2...13.2 Hz: +/- 1 mm
Tamperproof of settingsProtected by access code
Earth-leakage time delayInstantaneous for 0.03 A Adjustable 0...4.5 s for 0.03...30 A adjustable in step of 10 ms
Earth-leakage sensitivity0.03...1 A, adjustable in step of 0.001 A 1...30 A, adjustable in step of 0.1 A
Signal contacts composition1 C/O alarm fail-safe 1 NO pre-alarm fail-safe
Environmental characteristicExposure to damp heat not in service conforming to IEC 60068-2-30 Exposure to damp heat in service conforming to IEC 60068-2-56 Salt mist conforming to IEC 60068-2-52
Electromagnetic compatibilityConducted and radiated emissions: , B, conforming to CISPR 11 Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6 Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2 High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5 Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4 Radiated susceptibility: , 3, conforming to IEC 61000-4-3
Monitored distribution system1000 V - AC at 50/60 Hz (maximum) 1000 V - AC at 400 Hz (maximum)
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-25...55 °C
MPN
LV481004