Schneider Electric LV481016
MPNLV481016
Active
Closed toroid B type, VigiPacT, TB60P, inner diameter 60mm, rated current 160A
$1,534.95Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Current sensor type | B type closed toroid |
| Product or component type | Earth leakage current sensor |
| Voltage | 800 V |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Residual short-circuit withstand current | 36 kA / 0.5 s conforming to IEC 60947-2 |
| [Icw] rated short-time withstand current | 25 kA for 0.5 s |
| [Ie] rated operational current | 160 A |
| Network frequency | 50/60 Hz 0...2000 Hz |
| IP degree of protection | Body: IP40 Connectors: IP20 |
| Mounting mode | Fixed (plain backplate) Fixed (DIN rail) |
| Connections - terminals | Prefabricated connection |
| Pollution degree | Level 2 conforming to IEC 60664-1 |
All specifications
| Parameter | Value |
|---|---|
| Depth | 78 mm |
| Width | 126 mm |
| Height | 151 mm |
| Standards | IEC 60947-2 |
| Range | VigiPacT |
| Diameter | 60 mm inner: |
| Device short name | TB60P |
| Device application | Equipment monitoring and control |
| Overvoltage category | III |
| Environmental characteristic | Exposure to damp heat in service: category C2: 48 hours conforming to IEC 60068-2-56 Exposure to damp heat not in service (25...55 °C, RH 95 %) : 28 cycles conforming to IEC 60068-2-30 Salt mist: Kb/2 conforming to IEC 60068-2-52 |
| Ambient air temperature for storage | -25...70 °C |
| Ambient air temperature for operation | -25...70 °C |
MPN
LV481016