Skip to main content
Schneider Electric LV847138

Schneider LV847138 Masterpact Circuit Breaker

MPNLV847138
Active

Circuit Breaker Masterpact

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LV847138 key specifications
ParameterValue
Control typePush-button
Performance typeH2 50 kA 415 V AC
Product or component typeCircuit breaker
Voltage1000 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage12 kV
[Icw] rated short-time withstand current42 kA 0.5 s 42 kA 1 s 24 kA 3 s
Line rated current1000 A 104 °F (40 °C)
[Ics] rated service breaking capacity50 kA 220/415 V AC 50/60 Hz 50 kA 440 V AC 50/60 Hz 42 kA 500/525 V AC 50/60 Hz 42 kA 660/690 V AC 50/60 Hz
[Icm] rated short-circuit making capacity105 kA 220/415 V AC 50/60 Hz 105 kA 440 V AC 50/60 Hz 88 kA 500/525 V AC 50/60 Hz 88 kA 660/690 V AC 50/60 Hz
[Icu] rated ultimate short-circuit breaking capacity50 kA 220/415 V AC 50/60 Hz 50 kA 440 V AC 50/60 Hz 42 kA 500/525 V AC 50/60 Hz 42 kA 660/690 V AC 50/60 Hz
Power dissipation in80 W

All specifications

LV847138 additional specifications
ParameterValue
Poles description4P
IP degree of protectionIP30 conforming to EN 60529
Mounting modeFixed
Mounting supportRails Base plate
Connection pitch2.8 in (70 mm)
Upside connectionFront Rear
Downside connectionFront Rear
Maximum closing response time50 ms
Pollution degree3 IEC 60947-1
Operating altitude0...6561.68 ft (0...2000 m) without derating 2000...5000 m with derating
Depth8.2 in (209 mm)
Width13.6 in (346 mm)
Height11.9 in (301 mm)
Electrical durability3000 cycles 690 V AC 50/60 Hz EN/IEC 60947-2 6000 cycles 440 V AC 50/60 Hz EN/IEC 60947-2 AC-23A 3000 cycles 690 V AC 50/60 Hz EN/IEC 60947-3 AC-23A 6000 cycles 440 V AC 50/60 Hz EN/IEC 60947-3 AC-3 6000 cycles 440 V AC 50/60 Hz EN/IEC 60947-3
Mechanical durability12500 cycles with periodic preventive maintenance
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12
RangeMasterPacT
Control unitWithout control unit
Sensor rating400 A 630 A 800 A 1000 A
Neutral positionLeft
Device short nameMTZ1 10 H2
Device applicationPower distribution protection
Selectivity categoryCategory B
Maximum breaking time25 ms
Suitability for isolationYes EN/IEC 60947-2
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)
Integrated instantaneous protection (DIN in kA peak)81...99 kA
MPN
LV847138