The MGN60543 is a C60N miniature circuit breaker from the Schneider Electric Multi9 range, a D-curve thermal-magnetic unit rated 1 A at 50 °C with 4 protected poles. It snaps onto a 35 mm symmetrical DIN rail, occupies 8 x 9 mm pitches (72 mm wide), and is built to EN/IEC 60947-2, Category A. At 1 A, this is a low-current branch or control-circuit protector, not a main feeder.
Breaking capacity and what it means for your panel
Rated Icu (ultimate breaking capacity) hits 20 kA at 240 V AC phase-to-phase, 10 kA at 415 V, and 6 kA at 440 V — all per EN/IEC 60947-2. The Ics (service breaking capacity) is 75 % of those figures: 15 kA at 240 V, 7.5 kA at 415 V, 4.5 kA at 440 V. The 4-pole version (4P) switches all phases and neutral; the separate earth-leakage block (Vigi add-on) is an option, not built in.
Integration notes for the panel builder
Mounts fixed on 35 mm DIN rail. The toggle gives local ON/OFF indication and a contact position indicator confirms the state.