Analog Input Module, 8 In, Current, 1/2 wires, Loop Power, Hardened, Modicon Edge I/O NTS

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

NTSACI0802XH key specifications
ParameterValue
Type of cableShielded cable
Range of productModicon Edge I/O NTS
Power supply typeBus power from power supply bus (24 Vdc) Field power from power supply field (24 Vdc)
Analogue input typeCurrent +/- 20 mA Current 0...20 mA Current 4...20 mA
Input protection typeOver current / miswiring protection per channel for current input
Product or component typeAnalog input module
Rated operational voltage limits20.4...28.8 V DC
Typical current consumption36 mA 24 V DC on the Bus current 24 mA 24 V DC on the internal field current minimum 208.8 mA 24 V DC on the internal field current maximum
Sensor power supply19.2...30 V DC Loop power
Power dissipation in2.3 W maximum at 24 V DC
Sensor power supply protectionOver current protection per channel Short circuit protection on loop power supply per channel
Isolation between field power and bus1500 V AC

All specifications

NTSACI0802XH additional specifications
ParameterValue
IP degree of protectionIP20
Mounting supportbase
Maximum cable distance between devicesShielded cable <3280.8 ft (1000 m) current input
Pollution degree2
Shock resistance15 g 11 ms with and without accessory)
Relative humidity5...95 % without condensation
Operating altitude0...6561.68 ft (0...2000 m) without derating 2000...5000 m with derating
Vibration resistance1 g without accessory 2 g with accessory
Depth2.7 in (69 mm)
Width1.2 in (30 mm)
Height4.8 in (121 mm)
Housing colourGrey
StandardsEN/IEC 61131-2 EN 61010-2-201 UL 61010-2-201 IACS E10 EN/IEC 61000-6-5 EN/IEC 61850-3 EN/IEC 60079-0 EN 50155 EN 50121-4 EN 50121-5
MarkingCE UKCA CULus RCM
CategoryUS1PC3318214
LSB value0.61 µA, +/-20 mA 0.61 µA, 0...20 mA 0.49 µA, 4...20 mA
Directives2014/30/EU - electromagnetic compatibility 2014/34/EU - ATEX directive 2014/35/EU
Non-linearity<= 0.01 % FS voltage/current
Operating modeIsochronous/Asynchronous
Input impedance250 Ohm + internal current protector 10 Ohm typical
Input diagnosticUnderflow error per channel Overflow error per channel Broken wire error per channel Hardware error per channel Calibration error per channel Loop power supply error per channel Internal field power supply error per channel
Local signalling1 LED green module operating (RUN) 1 LED per channel green channel diagnostic 1 LED red module error (ERR)
Input wiring mode1 or 2 wires
Measurement error<= 0.3 % FS - 20...60 °C
Sampling duration1.595 ms per module
Temperature drift± 0.004 % FS/ °C
Device applicationIndustrial application in severe environment
Mandatory accessoryNTSXBA0200H base NTSXTB18_0_H terminal block
Protective treatmentConformal coating
Analogue input number8
Common mode rejection90 dB
Hot swapping fallbackYes
Analogue input resolution15 bits + sign
Permitted overload on inputs30 V at 50 mA maximum current
Isolation between channels and bus1500 V AC
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Ambient air temperature for operation-4...140 °F (-20...60 °C)
Isolation between channels and field pwrNo
MPN
NTSACI0802XH