Skip to main content
Schneider Electric NTSART0404XH

Schneider Electric NTSART0404XH

MPNNTSART0404XH
Active

Temperature Input Module, 4 Differential In, RTD, ThC, mV, 2/3/4 wires, Hardened, Modicon Edge I/O NTS

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

NTSART0404XH key specifications
ParameterValue
Type of cableShielded cable
Range of productModicon Edge I/O NTS
Power supply typeBus power from power supply bus (24 Vdc) Field power from power supply field (24 Vdc)
Analogue input typeVoltage +/- 40 mV Voltage +/- 80 mV Voltage +/- 160 mV Voltage +/- 320 mV Voltage +/- 640 mV Voltage +/- 1.28 V RTD Ni 100/Ni 1000 RTD Pt 100/Pt 1000 RTD Cu 10/50/100 RTD JPt 100/1000 RTD high precision Cu50/100, Ni100/1000, Pt100/1000 Resistor 150/300/600/2000/4500 Ohm Thermocouple type J/K/R/S/B/T/N/E/C/L/U
Input protection typeOver voltage protection
Product or component typeTemperature input module
Rated operational voltage limits20.4...28.8 V
Isolation between field power and bus1500 V AC
IP degree of protectionIP20
Mounting supportbase
Maximum cable distance between devicesShielded cable Shielded cable <656.2 ft (200 m)
Pollution degree2

All specifications

NTSART0404XH additional specifications
ParameterValue
Shock resistance15 g 11 ms with and without accessory)
Relative humidity5...95 % without condensation
Operating altitude0...6561.68 ft (0...2000 m) 2000...5000 m with derating
Vibration resistance1 g without accessory 2 g with accessory
Depth2.7 in (69 mm)
Width0.6 in (15 mm)
Height3.9 in (100 mm)
Housing colourGrey
Product weight0.108 lb(US) (0.049 kg)
StandardsEN/IEC 61131-2 EN 61010-2-201 UL 61010-2-201 IACS E10 EN/IEC 61000-6-5 EN/IEC 61850-3 EN/IEC 60079-0 EN 50155 EN 50121-4 EN 50121-5
MarkingCE UKCA CULus RCM
CategoryUS1PC3318214
Directives2014/30/EU - electromagnetic compatibility 2014/34/EU - ATEX directive 2014/35/EU
Non-linearity<= 0.01 % FS thermocouple/RTD input
Operating modeAsynchronous
Input impedance1 MOhm typical
Input diagnosticUnderflow error per channel Overflow error per channel Broken wire error per channel Hardware error per channel Calibration error per channel CJC error per channel Internal field power supply error per channel
Local signalling1 LED green module operating (RUN) 1 LED per channel green channel diagnostic 1 LED red module error (ERR)
Input wiring mode2, 3 or 4 wires for RTD and resistance inputs 2-wire for thermocouple and voltage inputs
Measurement error<= 0.10 % FS -20...60 °C (short time sampling)
Sampling duration60 ms at 50Hz rejection per channel 60 ms at 60Hz rejection per channel 40 ms channel switch time with short time sampling 140 ms channel switch time with long time sampling
Temperature drift+/- 0.003 %/°C
Device applicationIndustrial application in severe environment
Mandatory accessoryNTSXBA0100H base NTSXTB18_0_H terminal block
Protective treatmentConformal coating
Analogue input number4
Common mode rejection100 dB
Hot swapping fallbackYes
Analogue input resolution16 bits with overflow
Environmental characteristicGas resistant Salt spray resistant
Permitted overload on inputs+/- 2.4 % over voltage range
Isolation between channels and bus1500 V AC
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Ambient air temperature for operation-40...158 °F (-40...70 °C)
Isolation between channels and field pwr1000 V AC
MPN