Specifications

NTSDAI0403H key specifications
ParameterValue
Range of productModicon Edge I/O NTS
Power supply typeBus power from power supply bus (24 Vdc) Field power from external power supply (24 Vac, 48 Vac or 48 Vdc)
Product or component typeDiscrete input module
Discrete input voltage24 V AC 48 V AC/DC
Voltage state 0 guaranteed= 2 mA
Voltage state 1 guaranteedFor 48 V AC >= 34 V AC For 24 V AC >= 14 V AC For 48 V DC >= 34 V DC
Rated operational voltage limits19.2...60 V DC 19.2...55.2 V AC 47...63 Hz
Discrete input current2.6 mA
Current state 0 guaranteed<= 2 mA
Typical current consumption30 mA 24 V DC on the Bus current 0 mA 24 V DC on the internal field current
Power dissipation in1.51 W maximum at 24 V DC
Discrete input frequency47...63 Hz

All specifications

NTSDAI0403H additional specifications
ParameterValue
IP degree of protectionIP20
Mounting supportbase
Response time on input5.8 ms (on to off) 9.8 ms (fixed)
Pollution degree2
Shock resistance15 g 11 ms with and without accessory)
Relative humidity5...95 % without condensation
Operating altitude0...6561.68 ft (0...2000 m) without derating 2000...5000 m with derating
Vibration resistance1 g without accessory 2 g with accessory
Depth2.7 in (69 mm)
Width0.6 in (15 mm)
Height3.9 in (100 mm)
Housing colourGrey
Product weight0.106 lb(US) (0.048 kg)
StandardsEN/IEC 61131-2 EN 61010-2-201 UL 61010-2-201 IACS E10 EN/IEC 61000-6-5, interface type 1 and type 2 EN/IEC 61850-3, location G EN/IEC 60079-0 EN 50155 EN 50121-4 EN 50121-5
MarkingCE UKCA CULus RCM
CategoryUS1PC3318214
Directives2014/30/EU - electromagnetic compatibility 2014/34/EU - ATEX directive 2014/35/EU
Operating modeAsynchronous
Input filtering9.28 ms (fixed)
Input diagnosticExternal power supply error per channel Broken wire error per channel
Local signalling1 LED (green) for module operating (RUN) 1 LED per channel (green) for channel diagnostic 1 LED (red) for module error (ERR)
Input wiring mode1, 2 or 3 wires
Device applicationIndustrial application in severe environment
Mandatory accessoryNTSXBA0100H base NTSXTB12_1_H terminal block
Protective treatmentConformal coating
Discrete input number4
Hot swapping fallbackYes
Group of input channels1 group
Discrete input compatibility4 type 1 conforming to IEC 61131-2
Environmental characteristicGas resistant CX & GX combined Salt spray resistant
Isolation between channels and bus3000 V AC
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Ambient air temperature for operation-40...158 °F (-40...70 °C)
Isolation between channels and ground3000 V AC