Skip to main content
Schneider Electric SOL40N3A200 — Miniature Circuit Breakers (MCB)

Schneider Electric SOL40N3A200 EasyPact Solar MCCB, 200 A, 5

MPNSOL40N3A200
Active

Schneider Electric EasyPact Solar MCCB, 3P, 200 A at 40 °C, TM-D thermal-magnetic trip, 50 kA at 800 V AC, fixed mount, screw terminals, Grey (RAL 7015).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

SOL40N3A200 — Identification
ParameterValue
Product range (series)EasyPact Solar MCCB
Product/component typeCircuit breaker
Device applicationDistribution
SOL40N3A200 — Ratings
ParameterValue
Rated current (In)200 A at 40 °C
Poles configuration3P
Rated operational voltage (Ue)800 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated insulation voltage (Ui)1250 V AC conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Overvoltage categoryIII
SOL40N3A200 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)4000 cycles at 800 V In
Mechanical durability (cycles)20000 cycles
SOL40N3A200 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
SOL40N3A200 — Environmental
ParameterValue
Operating ambient temperature-10...50 °C
Storage ambient temperature-35...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
SOL40N3A200 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H
SOL40N3A200 — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity50 kA Icu at 800 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ics] rated service short-circuit breaking capacity40 kA at 800 V AC 50/60 Hz conforming to EN/IEC 60947-2
SOL40N3A200 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The L (thermal) element handles overload protection; the I (magnetic) element handles short-circuit protection.

Where it fits in a panel

Fixed backplate mount, 120 mm wide × 205 mm tall × 105 mm deep. Screw terminals front-connected on both line and load sides. The 40 mm connection pitch matches standard busbar spacing. Horizontal or vertical mounting — no derating needed for orientation.

Rated insulation voltage 1250 V AC, operational voltage 800 V AC 50/60 Hz. Suitability for isolation marked per EN/IEC 60947-2. IP20 finger-safe terminals. Electrical durability 4000 cycles at rated voltage; mechanical durability 20,000 cycles.

Frequently asked questions

What is the interrupting rating of SOL40N3A200?

50 kA at 800 V AC, which is the performance level N rating for this EasyPact Solar MCCB.

What trip unit does SOL40N3A200 use?

A TM-D thermal-magnetic trip unit with LI protection: L for overload (thermal) and I for short-circuit (magnetic).

Where can I buy SOL40N3A200?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN
SOL40N3A200