Skip to main content
Schneider Electric TM200HSC206DF

Schneider TM200HSC206DF Modicon M238 Counter Module, 60 kHz, 24 V DC

MPNTM200HSC206DF
Obsolete

schneider TM200HSC206DF twido — now discontinued. Supplied from remaining channel stock; full specifications, lifecycle and same-series options are below.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

TM200HSC206DF key specifications
ParameterValue
Type of cableShielded cable
Range of productModicon M238 logic controller
Discrete input typeAuxiliary input IN_CAP Auxiliary input IN_EN Auxiliary input IN_REF High-speed IN_A High-speed IN_B High-speed IN_SYNC
Product or component typeCounter module
Maximum voltage drop<3 V at state 1
Discrete input voltage24 V DC
Discrete output voltage24 V DC 19.2...30 V
Voltage state 0 guaranteed<= 5 V
Voltage state 1 guaranteed15...30 V
Load current2 A per module 0.5 A per output
Current consumption<= 2 A 24 V DC external power supply
Discrete input current2 mA 11 V

All specifications

TM200HSC206DF additional specifications
ParameterValue
Discrete output current0.5 A
Maximum leakage current0.1 mA at state 0
Short-circuit protectionAutomatic reset after disappearance of fault
Current state 0 guaranteed<= 0.5 mA
Current state 1 guaranteed5 mA
Counting frequency60 kHz
Mounting support35 mm symmetrical DIN rail
Electrical connection2 spring terminal blocks
Response time on output<= 200 µs energisation/de-energisation
CategoryUS1PC1222531
Cycle time1 ms
Counting mode8 mode configurable
Fallback statusFaulty channel set to 0 Each channel held at its last value or set to the predefined value (0 or 1)
Load inductanceL = 0.5/I²F
Load capacitance50 µF
Local signalling1 display block
Number of modules3 counter modules per TM238 base
Input compatibilityIncremental signal encoder with 15...30 V source outputs 2 and 3-wire sensors (24 V)
Discrete input logicPositive logic (sink)
Discrete input number12 EN/IEC 61131-2 type 1
Discrete output logicPositive logic (source)
Discrete output number4
Application specific i (O)Frequency generator Downcounting Frequency meter Upcounting Period measurement Axis following
Counter inputs resolution31 bits + sign
Output overload protection0.5...1.5 A trip current with automatic reset after fault disappearance, per o/p
Isolation between channels and internal logic1500 V for 1 minute

Product details

Overview

How it compares

The TM200HSC206DF uses 2 spring terminal blocks for wiring, whereas the TM238CNTLSCT uses a removable screw connector — a difference in field wiring method, not in function.

Lifecycle

MPN
TM200HSC206DF