Skip to main content
Schneider Electric TM5SE4IOL

Schneider TM5SE4IOL IO-Link Master, 12.5mm wide

MPNTM5SE4IOL
Active

Schneider Electric Modicon TM5, Communication module, TM5SE4IOL, 4x IO-Link Master, 12.5 mm width, 75 mm depth, CE UL ATEX.

$149.00Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

TM5SE4IOL specifications
ParameterValue
Range of productModicon TM5
Product or component typeCommunication module
IP degree of protectionIP20
Communication port protocolIO-Link
Pollution degree2
Relative humidity5...95 % without condensation
Operating altitude0...2000 m
Vibration resistance1 gn (f = 8.4...150 Hz) on DIN rail 3.5 mm (f = 5...8.4 Hz) on DIN rail
Depth75 mm
Width12.5 mm
Height99 mm
StandardsCE UL ATEX II 3
MarkingCE UL
Ambient air temperature for storage-25...70 °C
Ambient air temperature for operation0...55 °C without derating (horizontal installation) 0...60 °C with derating factor (horizontal installation) 0...50 °C (vertical installation)

Product details

The TM5SE4IOL is a Modicon TM5 IO-Link master module with four ports, communicating at up to 230,4 kBit/s to compatible sensors and actuators. Its 12.5 mm width means it takes exactly one DIN-rail slot — helpful when you're packing multiple modules into a tight cabinet. Depth is 75 mm, so allow that much clearance from the rail to the gland plate or back wall.

Lifecycle and compliance — what's covered

It is marked CE, UL, and ATEX II 3. Operating temperature range is 0 to 55 °C without derating horizontally, up to 60 °C with derating, and 0 to 50 °C when mounted vertically. Keep ventilation within those numbers to avoid thermal issues.

Mounting and environment notes

Mounts directly on DIN rail; the 12.5 mm width leaves no wasted space — but verify your rail is grounded properly; that's a common return cause when modules fail on ungrounded rails. Vibration rated at 1 gn from 8.4 to 150 Hz on DIN rail, which suits most machine panels but not direct engine mount. IP20 protection means it's for clean, dry cabinets — not washdown areas or outdoor enclosures without additional protection.

Frequently asked questions

What is TM5SE4IOL's listed depth?

The depth is 75 mm from the DIN rail to the farthest point of the module.

What is TM5SE4IOL's listed width?

The width is 12.5 mm, which is one DIN-rail slot.

What compliance documentation does this brand provide for TM5SE4IOL?

The module is marked CE, UL, and ATEX II 3. These certifications are listed on the product label and cover industrial and hazardous-location installations.

MPN