Schneider Electric XPSMCMDO0016C1G
MPNXPSMCMDO0016C1G
Active
16 DIGITAL OUTPUT PLC, SIL1 EXPA
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →Specifications
| Parameter | Value |
|---|---|
| Load type | Resistive load |
| Output signal | 16 configurable diagnostic connection |
| Range of product | Preventa Safety automation |
| Discrete input type | Isolated |
| Discrete output type | DC |
| Product or component type | Safe output expansion module |
| Integrated connection type | Backplane expansion bus |
| Discrete input voltage | 24 V DC |
| Discrete output voltage | 24 V DC |
| Supply voltage | 24 V - 20...20 % DC |
| [Uimp] rated impulse withstand voltage | 4 kV IEC 61800-5-1 |
| Discrete output current | 100 mA |
All specifications
| Parameter | Value |
|---|---|
| Power consumption in | 3 W |
| Power dissipation in | 3 W |
| IP degree of protection | IP20 enclosure) |
| Mounting support | Omega 35 mm DIN rail EN 50022 |
| Cable cross section | 0.0003...0.004 in² (0.2...2.5 mm²) - AWG 24...AWG 14 flexible without cable end 0.0004...0.004 in² (0.25...2.5 mm²) - AWG 23...AWG 14 flexible with cable end, without bezel 0.0004...0.004 in² (0.25...2.5 mm²) - AWG 23...AWG 14 flexible with cable end, with bezel 0.0003...0.004 in² (0.2...2.5 mm²) - AWG 24...AWG 14 solid with cable end, without bezel 0.0008...0.002 in² (0.5...1 mm²) - AWG 20...AWG 18 flexible with cable end, with double bezel |
| Electrical connection | Spring terminal |
| Connections - terminals | 2 spring clamp terminals, removable terminal block |
| Number of terminal blocks | 6 |
| Pollution degree | 2 |
| Shock resistance | 10 gn 16 ms) 1000 shocks on each axis IEC 61496-1 |
| Relative humidity | 10...95 % |
| Vibration resistance | +/-0.35 mm (f= 10...55 Hz) conforming to IEC 61496-1 |
| Depth | 0.9 in (22.5 mm) |
| Width | 4.5 in (114.5 mm) |
| Height | 3.9 in (99 mm) |
| Standards | IEC 61508 IEC 61800-5-1 ISO 13849-1 IEC 62061 |
| Category | US1SAF222477 |
| Insulation | 250 V AC between power supply and housing IEC 61800-5-1 |
| Output load | 60 Ohm |
| Safety level | Can reach category 1 ISO 13849-1 Can reach PL = c ISO 13849-1 Can reach SIL 1 IEC 61508 SILCL 1 IEC 62061 |
| Service life | 20 year(s) |
| Quality labels | CE |
| Local signalling | 1 LED green PWR power ON 1 LED green RUN RUN (status) 1 LED red E IN internal error 1 LED red E EX external error 2 LEDs orange ADDR node address 16 LEDs green/red OUT output status |
| Device short name | XPSMCM |
| Group of channels | 16 single channel |
| Function of module | Monitoring safety actuators discrete output |
| Overvoltage category | II |
| Safety reliability data | DC > 60 % MTTFd = 772 years high PFHd = 6.61E-9 1/h |
| Electromagnetic compatibility | Electrostatic discharge immunity test - test level: 6 kV (on contact) conforming to IEC 61000-4-2 Electrostatic discharge immunity test - test level: 20 kV (on air) conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to IEC 61000-4-3 Susceptibility to electromagnetic fields - test level: 30 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3 |
| Ambient air temperature for storage | -4...185 °F (-20...85 °C) |
| Ambient air temperature for operation | 14...131 °F (-10...55 °C) |
MPN