It switches control loads in panels where you need extra contact sets beyond the main contactor's built-in auxiliaries. Rated AC-12 at 24 V for 10 A, it handles resistive pilot-duty loads like PLC inputs, relay coils, and indicator lamps. At 230 V AC-15 it carries 6 A; at 400 V AC-15 it carries 3 A — enough for contactor coils and solenoid valves in a typical control panel.
Snap-on or screw-mount onto DIN rail. The S00 footprint — 57.5 mm high, 90 mm wide, 72 mm deep — fits standard panel layouts.
Switching capacity and ratings
AC-12 rating is the headline figure — 10 A at 24 V — but the contactor also carries 1 A at 110 V, 0.27 A at 220 V, 6 A at 230 V, 3 A at 400 V, 2 A at 500 V, and 1 A at 690 V. These are the AC-15 utilization category values for inductive pilot-duty loads. The 50 Hz rated operational voltage is 230 V; at 60 Hz it's also 230 V. Mechanical endurance is 5 million operations typical — a solid number for a secondary contactor that cycles with the main. Shock resistance is 10g / 5 ms and 5g / 10 ms, adequate for panel-mounted gear in most industrial machinery.
No IP rating on the sides or rear, so side clearances of 0 mm are permissible for ganging.