SIRIUS auxiliary contactor, 4 NO, size S00
Rated 10 A at 24 V, with a surge voltage resistance of 6 kV and pollution degree 3, it handles the typical 24 VDC control loops found in industrial panels while maintaining clearance for dirty environments. Contact reliability is specified at one incorrect switching operation per 100 million cycles at 17 V, 1 mA — a figure that matters for PLC-level signal switching where dry-contact reliability is the real constraint.
Fastens via screw or snap-on onto a DIN rail; the 57.5 mm height and 90 mm width fit the standard S00 footprint, leaving the 72 mm depth for wiring clearance behind the panel door. Terminal capacity accepts solid conductors: 2x 0.5–1.5 mm², 2x 0.75–2.5 mm², or 2x 4 mm² — enough for daisy-chaining control wiring without extra junction blocks.