The magnet coil is rated at 24 VDC with a closing power of 3.3 W. Pick-up voltage is 0.85 x rated value (20.4 V), and drop-out is 0.1 x rated value (2.4 V) — the hold range is wide, but verify your control supply stays above the pick-up threshold under load.
Main and Auxiliary Contact Ratings
Main circuit spring-loaded terminals accept 2x (0.25 to 2.5 mm²) solid or stranded wire. The auxiliary contacts (1 NO + 1 NC) are each rated at 12 A; the NC contact is instantaneous (zero delay). For DC switching at 24 V, the maximum permissible current is 0.01 A — this is a signal-level rating, not for power DC loads. AC switching capacity varies by voltage: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V. Mechanical life is typical 30 million operations; maximum switching frequency at AC-1 is 1000 cycles per hour.