At 45 mm wide, 58 mm tall, and 73 mm deep, it fits standard panel layouts without crowding adjacent devices.
The S00 frame size accepts main contact wire from 20 to 12 AWG, and the screw terminals accept solid or stranded conductors from 0.5 to 4 mm², with options for two conductors per clamp. Switching frequency depends on duty class: 1,000 operations per hour at AC-1 (resistive), 750/h at AC-2 and AC-3 (motor starting and running), and 250/h at AC-4 (plugging or inching). For a molding-cell conveyor cycling every 30 seconds, AC-3 at 750/h gives headroom; a rapid-reversing application would need to stay under the AC-4 limit. The integrated auxiliary switch carries 10 A at 24 V, 2 A at 48/60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. That covers PLC-level feedback signals without an add-on block.