Skip to main content
Siemens 3RT2016-1BB41-ZW97 — Contactors

Siemens 3RT2016-1BB41-ZW97 SIRIUS Power Contactor, S00, 24 V

MPN3RT2016-1BB41-ZW97
Active

Siemens SIRIUS, power contactor, size S00, 24 V DC coil, screw-type terminals, 45 mm width, 58 mm height, 73 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RT2016-1BB41-ZW97 — Identification
ParameterValue
Contactor frame sizeS00
3RT2016-1BB41-ZW97 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V1 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2016-1BB41-ZW97 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RT2016-1BB41-ZW97 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2016-1BB41-ZW97 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)
Short-circuit coordination type 2, fusegG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2016-1BB41-ZW97 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid0.5 ... 4 mm²
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Side-by-side mountingYes
3RT2016-1BB41-ZW97 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2016-1BB41-ZW97 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2016-1BB41-ZW97 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth73 mm

Product details

It carries a 24 V DC coil and is rated for 10 A at 24 V, with a 1 hp rating at 230 V. The auxiliary switch is included, giving you a spare N/O or N/C for feedback or interlocking.

Wiring accepts solid or stranded conductors from 0.5 to 4 mm², and can take two conductors per terminal (2x 0.5…1.5 mm², 2x 0.75…2.5 mm², or 2x 4 mm²). Coil terminals are screw-type, so no special tools needed.

Switching performance and ratings

Switching frequency depends on duty: up to 1,000 operations per hour at AC-1 (resistive), 750/h at AC-2 and AC-3 (motor starting/running), and 250/h at AC-4 (plugging/inching). The AC-3e rating also sits at 750/h. For DC switching, the arcing time runs 10–15 ms, and the operate/release time at DC is 7–13 ms. Current ratings at other voltages: 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. The 1 hp at 230 V gives a quick motor-sizing reference. Mechanical life is typical 30 million operations. Coil operates at 0.8 x rated value (pickup) and holds at 1.1 x rated value (full-scale).

Frequently asked questions

What are the key dimensions of this contactor?

Width is 45 mm, height is 58 mm, and depth is 73 mm. It fits on a 35 mm DIN rail and requires 10 mm clearance upwards, forwards, and downwards, and 6 mm at the side.

What wire sizes does it accept?

Solid or stranded conductors from 0.5 to 4 mm². It can also take two conductors: 2x 0.5…1.5 mm², 2x 0.75…2.5 mm², or 2x 4 mm². Coil terminals are screw-type.

What is the switching frequency for motor duty?

At AC-3 (motor starting/running), the maximum switching frequency is 750 operations per hour. At AC-4 (plugging/inching), it drops to 250 operations per hour.

MPN
3RT2016-1BB41-ZW97