It mounts via screw or snap-on onto a 35 mm DIN rail per EN 60715, and the Size S00 footprint (70 mm high, 45 mm wide, 73 mm deep) keeps it compact for dense panel layouts. The coil is 24 VDC with spring-type terminals, so no screwdriver is needed for the coil wiring — just strip and push.
The main contacts are rated for 20 to 12 A (AC-3 duty), which covers small to medium motor loads up to 2 hp at 230 V. The AC-3 switching frequency maxes out at 750 operations per hour — adequate for most conveyor and pump cycles, but if you're doing frequent jogging or reversing (AC-4), that drops to 250 ops/h, so plan your duty cycle accordingly. The auxiliary contact block is built in, with breaking capacities ranging from 10 A at 24 V down to 0.2 A at 440 V — verify your pilot circuit voltage against the table to ensure clean dropout.
Wiring and Clearance Notes
For ventilation, maintain 10 mm clearance upward, downward, and forward, plus 6 mm at the sides — these are minimums for heat dissipation at full rated current.