3RT2018-2AP01-ZX95 - Siemens
CONTACTOR, AC-3, 7.5KW/400V, 1NO, AC 230V, 50/60 HZ, 3-POLE, SZ S00 SPRING-LOADED TERMINAL REUSABLE PACKAGING; PACKAGE = 120 UNIT(S)
Specifications
| Parameter | Value |
|---|---|
| Contactor frame size | S00 |
| Parameter | Value |
|---|---|
| Rated operational current, AC-12, max. | 10 A |
| Rated operational current, AC-4 @ 400 V | 11.5 A |
| Rated value @ 400 V | 3 A |
| Rated value @ 500 V | 2 A |
| Rated value @ 690 V | 1 A |
| Rated value @ 230 V | 2 hp |
| Rated value @ 24 V | 10 A |
| Rated value @ 60 V | 2 A |
| Rated value @ 110 V | 1 A |
| Rated value @ 220 V | 0.3 A |
| Parameter | Value |
|---|---|
| Control supply voltage type | AC |
| Rated value @ 50 Hz | 0.25 |
| Rated value @ 50 Hz | 230 V |
| Parameter | Value |
|---|---|
| Main poles | 3 |
| Main NO contacts | 3 |
| Auxiliary contact reliability | 1 faulty switching per 100 million (17 V, 1 mA) |
| Parameter | Value |
|---|---|
| Short-circuit coordination type 1, fuse | gG: 50A (690V,100kA), aM: 25A (690V,100kA), BS88: 50A (415V,80kA) |
| Short-circuit coordination type 2, fuse | gG: 25A (690V,100kA), aM: 20A (690V,100kA), BS88: 25A (415V,80kA) |
| Aux. switch short-circuit protection, fuse | gG: 10 A (500 V, 1 kA) |
| Parameter | Value |
|---|---|
| Main circuit connection | spring-loaded terminals |
| Aux. / control circuit connection | spring-loaded terminals |
| Conductor cross-section, solid | 0.5 ... 4 mm² |
| Conductor cross-section, solid or stranded | 2x (0,5 ... 4 mm²) |
| Conductor cross-section, finely stranded w/ ferrule | 2x (0.5 ... 2.5 mm²) |
| Mounting method | screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715 |
| Side-by-side mounting | Yes |
| Parameter | Value |
|---|---|
| Durability (operating cycles, typ.) | 30 000 000 |
| Durability with aux. switch block (cycles, typ.) | 10 000 000 |
| Parameter | Value |
|---|---|
| Operating temperature range | -25 ... +60 °C |
| Storage temperature range | -55 ... +80 °C |
| Installation altitude, max. | 2 000 m |
| Parameter | Value |
|---|---|
| Width | 45 mm |
| Height | 70 mm |
| Depth | 73 mm |
| Parameter | Value |
|---|---|
| At AC | 4 ... 15 ms |
Frequently asked questions
What is the coil voltage of Siemens 3RT2018-2AP01-ZX95?
Buyers must verify 230V AC 50/60Hz coil matches their control circuit before sourcing.
What does the -ZX95 suffix mean on a Siemens 3RT2018 contactor?
The suffix encodes the reusable-packaging 120-unit option, affecting order quantity and price.
What is the difference between 3RT2018-2AP01 and 3RT2018-2AP01-ZX95?
Engineers need to confirm whether the base MPN and -ZX95 variant are interchangeable or require separate ordering.
How many main contacts and auxiliary contacts does the 3RT2018-2AP01-ZX95 have?
3-pole main plus 1NO auxiliary must fit the panel I/O design and wiring schematic.
Is the Siemens 3RT2018-2AP01-ZX95 still in production?
Active product status matters for lifecycle planning and warranty support decisions.
Where can I buy 3RT2018-2AP01-ZX95 with confirmed stock?
Directs buyers to authorized Siemens distributors carrying the reusable-packaging bulk SKU.