Switching performance and life
Rated for 1 000 switching cycles per hour under AC-1, AC-2, AC-3, and AC-3e duty, and 300 cycles per hour under AC-4 duty — the heavier AC-4 category (frequent starting/plugging) halves the allowable rate. Arcing time is 10 ms. For DC switching, the contactor handles 6 A at 24 V, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. At 230 V it's rated for 1 hp motor load.
The coil screw terminals accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) fine-stranded. Torque for main contacts is 16 to 8 Nm. No auxiliary switch is built into this variant — if you need aux contacts, that's a separate order.