Depth is 97 mm, so it clears standard 100 mm enclosure depths without issue. Mounting is screw or snap-on onto 35 mm DIN rail per DIN EN 60715, and the mounting position allows ±180° rotation on a vertical surface plus ±22.5° tilt — useful when panel layout forces an unconventional orientation.
Wire range accepts solid or stranded conductors from 1 to 10 mm², and for the auxiliary contacts the spec allows two conductors per terminal (2x 0.5–1.5 mm² or 2x 0.75–2.5 mm²). That covers most motor-circuit wiring up to 4 mm² without needing a ferrule change. The contactor is rated for switching frequencies: up to 1000 cycles per hour in AC-1 resistive duty, 750 cycles/hour in AC-3 motor-starting duty, and 250 cycles/hour in AC-4 reversing/plugging duty. For a conveyor or pump start-stop, the AC-3 rate is the one that governs — 750 cycles/hour is enough for a fast-cycling line but not a servo-like application.
That 6 mm side gap is tighter than some older contactor families — if you're retrofitting into a panel that had a wider frame, verify the side spacing before committing.