Siemens 3VA1010-2ED36-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1010-2ED36-0AF0 MCCB, 100 A, 52.5 kA at 2

MPN3VA1010-2ED36-0AF0

Siemens SENTRON 3VA1010-2ED36-0AF0, molded case circuit breaker, 3-pole, 100 A rated continuous current (Iu), TM210 thermal-magnetic release, 52.5 kA breaking capacity at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1010-2ED36-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1010-2ED36-0AF0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1010-2ED36-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1010-2ED36-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-2ED36-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1010-2ED36-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-2ED36-0AF0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The 3VA1010-2ED36-0AF0: This MCCB delivers 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. For a 480 V panel, the relevant figure is the 415 V or 440 V rating; pick the one that brackets your line-to-line voltage. The 690 V rating matters only if you're on a 600 V class system. These numbers govern your SCCR (short-circuit current rating) compliance per NEC 110.10 and UL 508A.

Thermal derating — don't size by the nameplate alone

At 55 °C it derates to 96 A, at 60 °C to 94 A, at 65 °C to 92 A, and at 70 °C to 90 A.

Auxiliary contacts and trip indication

The trip alarm signals when the breaker has opened on a fault — useful for remote annunciation or PLC input.

No rewiring needed if you're swapping from another 3-pole SENTRON 3VA frame; the line and load lug centers match the series pattern.

MPN