Its breaking capacity reaches 52.5 kA at 240 V AC, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — figures that define the available fault current it can safely interrupt at each voltage level without upstream coordination failure. The 100 A rating holds across ambient temperatures from 40 °C to 50 °C without derating; above that, the curve steps down to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. For a panel running warm — say, a packed enclosure near a drive cabinet — that derating profile is the number that governs the actual load you can protect.
The 3VA1010-2ED36-0BH0 measures 70 mm deep, 76.2 mm wide, and 130 mm tall — a 3-pole footprint that mounts on a DIN rail or directly to a backplate via the SENTRON mounting accessories.
The auxiliary contact block is specified as order code 3VA9608-0BB11 for replacement or expansion. The UVR drops the breaker on loss of control voltage — standard for emergency-stop circuits or undervoltage protection schemes where the load must not auto-reclose.