SENTRON 3VA1010-3ED36-0KA0 — 100 A MCCB with Shunt Trip for Line Protection
Its TM210 thermal-magnetic release handles overload and short-circuit protection, and the integrated shunt trip (STL) allows remote tripping via a control signal — useful for emergency-stop or supervisory shutdown circuits.
Breaking Capacity and Voltage Ratings
Interrupting capacity drops with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V.
Rated 100 A from 40 °C through 50 °C, then derates linearly: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C.
Physical Fit and Mounting