Its TM210 overcurrent release combines a thermal bimetal for overload protection and a magnetic coil for short-circuit response — a fixed-trip design that doesn't require adjustment in the field. Breaking capacity runs 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V — numbers that tell you this breaker handles high fault current at lower voltages but derates sharply above 440 V.
Above that it steps down: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. Maximum power loss is 25 W — useful to know for enclosure heat calculations when the panel runs near the upper end of the operating range.
The 3VA1010-3ED36-0AA0 measures 130 mm high, 76.2 mm wide, and 70 mm deep — a standard 3-pole MCCB footprint that mounts on a DIN rail or directly to a backplate with the provided screw terminals.