Skip to main content
Siemens 3VA1020-3ED36-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1020-3ED36-0JA0 SENTRON MCCB, 20 A, 3-Pole, 75.6

MPN3VA1020-3ED36-0JA0

Siemens SENTRON 3VA, molded case circuit breaker, 3-pole, 20 A, TM210 thermal-magnetic release, 75.6 kA interrupting rating at 240 V, 70 mm depth, IP40 front protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1020-3ED36-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1020-3ED36-0JA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C19.2 A
Current at 60 °C18.8 A
Current at 65 °C18.4 A
Current at 70 °C18 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V7.5 kA
3VA1020-3ED36-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1020-3ED36-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1020-3ED36-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1020-3ED36-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1020-3ED36-0JA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Siemens 3VA1020-3ED36-0JA0 — 20 A MCCB with TM210 Release

It's built for line protection — the core job of clearing overloads and short circuits in a distribution panel without taking out upstream gear. The interrupting ratings climb with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and still 7.5 kA at 690 V. That's enough SCCR headroom for most industrial secondary distribution — a 240 V panel with a 65 kA available fault current is comfortably covered, and the 415 V figure handles heavy European-style networks. Thermal derating is minimal up to 50 °C — the breaker holds its full 20 A rating. Past that it drops gradually to 18 A at 70 °C, which is the maximum operating ambient. If the panel runs hot near a furnace or in a sealed enclosure, that derating curve matters for the BOM line.

Footprint is 76.2 mm wide by 130 mm tall by 70 mm deep — a standard 3-pole MCCB slice that fits most DIN-rail or backplate layouts without surprises. If the panel spec calls for those, you'd step to a different suffix.

Frequently asked questions

What is the closest functional second-source for 3VA1020-3ED36-0JA0?

The closest functional peer is 3VA1020-3ED36-0AA0, which shares the same 20 A rating, 3-pole count, TM210 release, and interrupting ratings. The difference is the auxiliary release fit — the -0JA0 carries a shunt trip (STL), while the -0AA0 does not. They drop into the same panel footprint without rewiring, but the shunt trip wiring differs.

What are the key interrupting ratings for this MCCB?

75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V. These cover most industrial secondary distribution scenarios.

How do I get current pricing and availability for 3VA1020-3ED36-0JA0?

Submit an RFQ through this listing. We source the part to order against your request and confirm current pricing and availability at quote time — no stock figures or lead-time numbers on the page.

Will 3VA1020-3ED36-0JA0 drop into a panel specified for 3VA1020-3ED36-0AA0?

Yes, the physical footprint is identical — same 76.2 mm width, 130 mm height, 70 mm depth. The only difference is the shunt trip (STL) on the -0JA0, which requires an additional control wire pair. No rewiring of the power connections needed.

MPN
3VA1020-3ED36-0JA0