It holds its full 40 A rating through 50 °C; above that it derates to 38.4 A at 55 °C and 36 A at 70 °C — relevant if the breaker sits in a warm enclosure near other heat sources. Breaking capacity runs 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. For a 480 V line the 415 V figure is the closest reference; the 690 V rating confirms it handles higher-voltage industrial feeds where fault current is lower. It does not carry an undervoltage release, phase-failure detection, or ground-fault monitoring — those are separate add-on options in the 3VA family. Front protection is IP40, so it suits dry indoor panel environments.
Siemens 3VA1040-2ED32-0JC0 SENTRON MCCB, 40 A, 52.5 kA
Siemens SENTRON, Molded case circuit breaker, 3VA1040-2ED32-0JC0, 3-pole, 40 A, 52.5 kA at 240 V, TM210 release, shunt trip, 2 auxiliary switches HQ.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Product version | Line protection |
| Integrated auxiliary / alarm switch ref. | 3VA9988-0AA12 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Current at 40 °C | 40 A |
| Current at 45 °C | 40 A |
| Current at 50 °C | 40 A |
| Current at 55 °C | 38.4 A |
| Current at 60 °C | 37.6 A |
| Current at 65 °C | 36.8 A |
| Current at 70 °C | 36 A |
| Switching capacity class | B |
| Breaking capacity at 240 V | 52.5 kA |
| Breaking capacity at 415 V | 32 kA |
| Breaking capacity at 440 V | 13.6 kA |
| Breaking capacity at 690 V | 7.5 kA |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | TM210 |
| Parameter | Value |
|---|---|
| Main circuit connection type | lug terminal |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | Yes |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | No |
| Auxiliary CO contacts | 2 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Height | 130 mm |
| Width | 76.2 mm |
| Depth | 70 mm |
Product details
Frequently asked questions
What is the breaking capacity of 3VA1040-2ED32-0JC0 at 415 V?
At 415 V the breaking capacity is 32 kA. At 240 V it is 52.5 kA, at 440 V it is 13.6 kA, and at 690 V it is 7.5 kA.
Does this MCCB include a shunt trip?
Yes, it includes a shunt trip (STL) for remote opening. It also carries two HQ auxiliary switches for status indication. It does not include an undervoltage release or ground-fault monitoring.
Where can I buy 3VA1040-2ED32-0JC0 and how is it quoted?
This part is sourced through independent distribution channels and quoted to order against an RFQ. Submit an RFQ with your target quantity and delivery timeline; availability and current pricing are confirmed at quote time.