Skip to main content
Siemens 3VA1050-2ED32-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1050-2ED32-0BH0 SENTRON MCCB, 50 A, 52.5 kA at 24

MPN3VA1050-2ED32-0BH0

Siemens SENTRON 3VA1050-2ED32-0BH0, molded case circuit breaker, 3-pole, Line protection, 50 A rated current, TM210 overcurrent release, 52.5 kA breaking capacity at 240 V, with undervoltage release and 2 auxiliary switches + 1 trip alarm switch HQ.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1050-2ED32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1050-2ED32-0BH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C48 A
Current at 60 °C47 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1050-2ED32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1050-2ED32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1050-2ED32-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1050-2ED32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1050-2ED32-0BH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Breaking capacity varies by system voltage: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — so at 415 V it comfortably clears a 32 kA prospective fault, which covers most industrial low-voltage distribution panels.

Thermal derating and operating conditions

Above that it derates linearly: 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C — so in a hot panel near the top of a cabinet, expect to lose about 10 % of the rating. The IP40 front protection means it's splash-proof from the front but not sealed — mount it in a cabinet, not outdoors.

Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a standard 3-pole MCCB footprint for DIN-rail or screw-mount panels. The 76.2 mm width is 3 module spaces (1 module = 25.4 mm) on a DIN rail, so it occupies three 18 mm slots in a typical distribution board.

Frequently asked questions

Where can I buy 3VA1050-2ED32-0BH0 and how do I get a price?

This part is available to order through independent distribution. Submit an RFQ for current pricing and availability; the quote will reflect the market at that time.

What is the breaking capacity of 3VA1050-2ED32-0BH0 at 415 V?

At 415 V the breaking capacity is 32 kA, which is the standard rating for most European 400 V industrial distribution panels.

What auxiliary contacts are fitted on 3VA1050-2ED32-0BH0?

It comes with 2 auxiliary switches plus 1 trip alarm switch (HQ configuration), providing both status and alarm feedback.

What is the ambient temperature derating for 3VA1050-2ED32-0BH0?

Full 50 A rating holds from 40 °C to 50 °C. Above 50 °C it derates to 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C.

MPN