Skip to main content
Siemens 3VA1063-3ED32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-3ED32-0AC0 SENTRON MCCB, 63 A, 75.6 kA

MPN3VA1063-3ED32-0AC0

Siemens SENTRON 3VA molded case circuit breaker, 3VA1063-3ED32-0AC0, 3-pole, 63 A at 40 °C, TM210 thermal-magnetic release, 75.6 kA interrupting at 240 V AC, line protection design.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1063-3ED32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10633ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1063-3ED32-0AC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.17.3 W
3VA1063-3ED32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1063-3ED32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1063-3ED32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1063-3ED32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1063-3ED32-0AC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The 3VA1063-3ED32-0AC0 is a SENTRON molded case circuit breaker rated 63 A continuous at 40 °C, with no derating needed up to 50 °C — at 55 °C it still carries 62 A, and at 70 °C it holds 58 A. That thermal curve means this MCCB handles full load in a warm enclosure without tripping prematurely. Interrupting capacity hits 75.6 kA at 240 V and 52.5 kA at 415 V — figures that cover high-fault commercial and industrial service entrances. The 3-pole format and 70 x 76.2 x 130 mm footprint fit standard DIN-rail or panel-mount layouts — no special adapter needed for a typical MCC bucket.

Integration notes

No undervoltage release or shunt trip is fitted from the factory — those are add-on accessories if needed for emergency-off or undervoltage protection schemes. Maximum power loss is 17.3 W, so in a densely packed panel the heat load is manageable but not negligible — account for it in the thermal budget if the MCCB sits beside other high-draw devices.

Frequently asked questions

How do I get current pricing and availability for 3VA1063-3ED32-0AC0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the interrupting capacity of this breaker at 240 V?

75.6 kA at 240 V AC. That drops to 52.5 kA at 415 V and 32 kA at 440 V — still well above typical fault levels for most commercial and light industrial panels.

Will 3VA1063-3ED32-0AC0 drop into a panel specified around 3VA1110-5ED36-0AC0?

Physically the same 3VA frame — same width, depth, and height — so it mounts in the same panel cutout and DIN-rail footprint. The difference is rating: this one is 63 A with a TM210 release, while the 3VA1110-5ED36-0AC0 is a higher-current variant. Check your load and fault-current coordination before swapping.

MPN