Siemens 3VA1063-3ED32-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-3ED32-0AD0 SENTRON MCCB, 63 A, 75.6 kA at 24

MPN3VA1063-3ED32-0AD0

Siemens SENTRON 3VA1063-3ED32-0AD0, 3-pole molded case circuit breaker, 63 A rated current, 75.6 kA breaking capacity at 240 V, TM210 thermal-magnetic release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1063-3ED32-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1063-3ED32-0AD0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V7.5 kA

Protection & Trip Unit

3VA1063-3ED32-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1063-3ED32-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1063-3ED32-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3

Environmental

3VA1063-3ED32-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1063-3ED32-0AD0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What the ratings mean for fit

The Siemens SENTRON 3VA1063-3ED32-0AD0 is a 3-pole molded case circuit breaker rated for 63 A continuous current at 40 °C, with a TM210 thermal-magnetic release. The breaking capacity is 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V — these are the fault currents it can safely interrupt at each voltage level, so the panel's available fault current at the breaker's line side must fall within these limits for the system to coordinate. The 63 A rating holds steady up to 50 °C; above that it derates to 60.48 A at 55 °C and 56.7 A at 70 °C, which matters if the breaker lives in a hot enclosure. The IP40 front protection means it's fine for a dry indoor panel but not for washdown areas.

Panel fit and integration

The 3VA1063-3ED32-0AD0 measures 130 mm high, 76.2 mm wide, and 70 mm deep — a standard SENTRON 3VA footprint that drops into a DIN-rail or screw-mounted panel slot. The width is a tight 3-inch (76.2 mm) per pole, so a 3-pole unit takes about 3 inches of rail space. Operating temperature range is -25 °C to 70 °C; storage range -40 °C to 80 °C. The IP40 front keeps dust out of the trip mechanism in a typical enclosure.

Frequently asked questions

Where can I buy 3VA1063-3ED32-0AD0 and get a price?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1063-3ED32-0AD0 at 415 V?

The breaking capacity is 52.5 kA at 415 V.

Does 3VA1063-3ED32-0AD0 include auxiliary contacts?

Yes, it comes with 3 auxiliary switches HQ built in.

MPN