Siemens 3VA1110-3EF36-0AB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-3EF36-0AB0 SENTRON MCCB, 100 A, 3-Pole

MPN3VA1110-3EF36-0AB0

Siemens SENTRON 3VA1110-3EF36-0AB0, molded case circuit breaker, 3-pole, 100 A, TM240 thermal-magnetic trip, line protection, 70 mm depth, 76.2 mm width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1110-3EF36-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA11
3VA1110-3EF36-0AB0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA
3VA1110-3EF36-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1110-3EF36-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-3EF36-0AB0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1110-3EF36-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-3EF36-0AB0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The 100 A rating holds across 40 °C to 50 °C ambient; above that it derates stepwise to 90 A at 70 °C. Interrupting capacity is specified at four voltage levels: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V. That spread tells you the breaker is sized for high-fault industrial distribution — the 75.6 kA figure at 240 V covers low-voltage transformer secondaries, while the 10.5 kA at 690 V still clears a substantial fault on 690 V plant networks.

Frequently asked questions

Where can I buy 3VA1110-3EF36-0AB0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time and price.

What is the interrupting capacity of this MCCB at 415 V?

At 415 V the 3VA1110-3EF36-0AB0 interrupts 52.5 kA. At 240 V it clears 75.6 kA, and at 690 V it still handles 10.5 kA.

Does 3VA1110-3EF36-0AB0 include auxiliary contacts?

Yes, it ships with two auxiliary switches (HP type) for status signaling.

MPN