Siemens 3VA1112-1AA32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-1AA32-0AH0 SENTRON Switch Disconnector, 125

MPN3VA1112-1AA32-0AH0

Siemens SENTRON 3VA1 IEC frame 160, 3-pole switch disconnector SD100, In=125 A, without overload or short-circuit protection, front busbar connection, 2 auxiliary switches HQ + 1 trip alarm switch HQ, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1112-1AA32-0AH0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1112-1AA32-0AH0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W
3VA1112-1AA32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-1AA32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1112-1AA32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-1AA32-0AH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What this SENTRON switch disconnector is — and isn't

The Siemens 3VA1112-1AA32-0AH0 is a 3-pole switch disconnector in the SENTRON 3VA1 family, IEC frame 160, rated for 125 A continuous current (Iu). It is not a molded case circuit breaker — there is no overload release or short-circuit protection built in. This is a pure isolation and switching device, intended for applications where the upstream protection is already provided by a separate MCCB or fuse, and you need a local disconnect for safe maintenance isolation.

Termination and aux contact configuration

Main circuit connection is via busbar connection on the front terminals — this is a panel-mount part designed for busbar systems, not cable lugs. Motor drive is available as an optional field-addable extension. Dimensions are 70 mm deep, 76.2 mm wide, 130 mm tall — the same footprint as the 3VA1 MCCB variants, so it drops into the same panel cutout and busbar layout.

Frequently asked questions

Will 3VA1112-1AA32-0AH0 fit into a panel designed for 3VA1010-2ED36-0AC0?

Yes — both parts share identical dimensions (70 mm deep, 76.2 mm wide, 130 mm tall) and the same front-terminal busbar connection arrangement, so the switch disconnector drops into the same panel cutout and busbar layout without rewiring.