Skip to main content
Siemens 3VA1112-5ED32-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-5ED32-0AF0 SENTRON MCCB, 125 A, 3-Pole

MPN3VA1112-5ED32-0AF0

Siemens SENTRON 3VA1112-5ED32-0AF0, 3-pole molded case circuit breaker, 125 A at 40 °C, TM210 overcurrent release, 187 kA breaking capacity at 240 V, line protection design.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1112-5ED32-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11125ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1112-5ED32-0AF0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.28.1 W
3VA1112-5ED32-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1112-5ED32-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-5ED32-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1112-5ED32-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-5ED32-0AF0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1112-5ED32-0AF0 is a 3-pole molded case circuit breaker rated for 125 A continuous current at 40 °C ambient, with a TM210 thermal-magnetic overcurrent release. Its interrupting capacity reaches 187 kA at 240 V AC, dropping to 121 kA at 415 V and 75.6 kA at 440 V — figures that cover most industrial distribution fault levels downstream of a transformer. This is a line-protection design (not motor-protection curve), so it suits feeder circuits, panel mains, and distribution subfeeds where the TM210 release provides short-circuit and overload protection. Built-in trip indicator speeds fault diagnosis — no need to guess which pole tripped. That covers remote status and alarm feedback without an add-on module.

Dimensions are 76.2 mm wide (3 in), 130 mm tall (5.12 in), 70 mm deep (2.76 in). The 3-pole width matches a standard 4-module DIN-rail slot at 18 mm per pole. Depth is shallow enough for 200 mm deep enclosures; verify gland-plate clearance for incoming cables.

Frequently asked questions

What is the interrupting capacity of 3VA1112-5ED32-0AF0 at 240 V?

187 kA at 240 V AC. At 415 V it is 121 kA, at 440 V it is 75.6 kA, and at 500 V or 690 V it is 17 kA.

Where can I buy 3VA1112-5ED32-0AF0 and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
3VA1112-5ED32-0AF0