Skip to main content
Siemens 3VA1132-3EF32-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-3EF32-0BA0 SENTRON MCCB, 32 A, 3-Pole, TM240

MPN3VA1132-3EF32-0BA0

Siemens SENTRON 3VA1132-3EF32-0BA0, molded case circuit breaker, 3-pole, 32 A rated continuous current, TM240 thermal-magnetic release, line protection version.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1132-3EF32-0BA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1132-3EF32-0BA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA
3VA1132-3EF32-0BA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1132-3EF32-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1132-3EF32-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1132-3EF32-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1132-3EF32-0BA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

This MCCB delivers 75.6 kA interrupting capacity at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V. For a 415 V distribution board, the 52.5 kA figure gives solid headroom above the typical 25–36 kA SCCR of most panelboards — you can place it downstream of a transformer without worrying about cascading failure on a high-fault event.

Thermal derating and ambient limits

Above 55 °C it derates: 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C. If your panel runs hot — near a drive or transformer — factor the derating into the continuous load.

The 76.2 mm width (3-inch pitch) matches standard MCCB mounting in most 600 V panelboards — it occupies three 25 mm pole spaces. No auxiliary contacts or communication module on this variant; the auxiliary trip is ordered separately (3VA9608-0BB11).

Frequently asked questions

Where can I buy 3VA1132-3EF32-0BA0 and what is the lead time?

This part is sourced to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time.

What is the breaking capacity of 3VA1132-3EF32-0BA0 at 415 V?

52.5 kA at 415 V. It also clears 75.6 kA at 240 V, 32 kA at 440 V, and 10.5 kA at 690 V.

Does 3VA1132-3EF32-0BA0 include an undervoltage release?

Yes, it comes with an undervoltage release (UVR) integrated. The auxiliary trip is ordered separately as 3VA9608-0BB11.

MPN
3VA1132-3EF32-0BA0