Skip to main content
Siemens 3VA1132-3EF32-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1132-3EF32-0BH0 MCCB, 32 A, 75.6 kA at 24

MPN3VA1132-3EF32-0BH0

Siemens SENTRON 3VA1132-3EF32-0BH0, molded case circuit breaker, 3-pole, 32 A, 75.6 kA at 240 V, line protection, TM240 release, with undervoltage release.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1132-3EF32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1132-3EF32-0BH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA
3VA1132-3EF32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1132-3EF32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1132-3EF32-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1132-3EF32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1132-3EF32-0BH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1132-3EF32-0BH0 is a 3-pole molded case circuit breaker rated for 32 A continuous current (Iu) at 40 °C, with a TM240 thermal-magnetic overcurrent release and an integrated undervoltage release (UVR). It's a line-protection device, so it's built for feeder and distribution duty — not motor-protection curves, not ground-fault monitoring. The interrupting ratings are solid: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V. That gives you real SCCR headroom for panel coordination studies, especially on 480 V or 415 V systems where the 52.5 kA figure covers most utility-fault scenarios.

Panel fit and physical integration

The 3VA1132-3EF32-0BH0 measures 70 mm deep, 76.2 mm wide, and 130 mm high.

Temperature derating — the real continuous current

Rated 32 A up to 50 °C. Above that, the TM240 release starts to back off: 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C.

Frequently asked questions

What is 3VA1132-3EF32-0BH0's listed depth?

The depth is 70 mm.

What is 3VA1132-3EF32-0BH0's listed width?

The width is 76.2 mm.

MPN
3VA1132-3EF32-0BH0