Skip to main content
Siemens 3VA1132-5EF36-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-5EF36-0CC0 SENTRON MCCB, 32 A, 187 kA at 240

MPN3VA1132-5EF36-0CC0

Siemens SENTRON 3VA1132-5EF36-0CC0, molded case circuit breaker, 3-pole, 32 A rated continuous current, 187 kA at 240 V, TM240 overcurrent release, undervoltage release, 2 auxiliary switches HQ.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1132-5EF36-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1132-5EF36-0CC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA
3VA1132-5EF36-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1132-5EF36-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1132-5EF36-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1132-5EF36-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1132-5EF36-0CC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1132-5EF36-0CC0 is a 3-pole molded case circuit breaker rated for line protection, with a rated continuous current Iu of 32 A that holds flat across 40 °C to 50 °C before a gentle thermal derating curve — at 70 °C it still carries 28.8 A. The interrupting capacity is the headline: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V. That kind of fault-clearing muscle means it can sit at the main distribution point in a high-fault industrial panel without needing upstream fuses to back it up. No communication function, no phase-failure detection — this is a straightforward, high-interrupting MCCB for a main feeder or large branch.

The 3VA1132-5EF36-0CC0 measures 76.2 mm wide, 130 mm high, and 70 mm deep — a standard SENTRON 3VA frame size that drops into a DIN-rail or screw-mounted panel cutout. The integrated undervoltage release (UVR) and the two HQ auxiliary switches (order code 3VA9608-0BB24 for the auxiliary trip block) are factory-fitted, so no field wiring of add-on modules.

Frequently asked questions

What is the closest functional second-source to 3VA1132-5EF36-0CC0?

The 3VA1112-5EF32-0CA0 is a similar SENTRON 3VA frame MCCB but with a lower interrupting capacity and different release configuration. It will not drop into the same panel without verifying the fault current rating and auxiliary wiring — the 3VA1132-5EF36-0CC0 carries 187 kA at 240 V, which is significantly higher than the 3VA1112-5EF32-0CA0's rating.

Where can I buy 3VA1132-5EF36-0CC0 and how is it quoted?

This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

MPN