The 3VA1132-5EF36-0DH0: The 32 A rating holds flat from 40 °C to 50 °C ambient, then derates to 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C. That's predictable and linear; the datasheet curve is clean.
Physical fit and auxiliary options
The can measures 76.2 mm wide, 130 mm tall, and 70 mm deep — standard 3-pole MCCB footprint for the SENTRON 3VA frame. That UVR means the breaker drops out if control voltage is lost, which is common for emergency-stop circuits or undervoltage protection schemes.