Interrupting capacity and thermal derating
At 415 V the rating drops to 154 kA, at 440 V to 121 kA, and at 690 V to 17 kA. The thermal-magnetic TM240 release holds full 32 A from 40 °C through 50 °C; above that it steps down: 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C.