The 3VA1132-6EF32-0DH0: This MCCB delivers 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V.
Thermal derating and panel temperature
Above that it derates linearly: 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C. If your panel ambient runs 55 °C, you lose about 1.3 A — plan the load accordingly. The TM240 release is fixed thermal-magnetic, not electronic, so the trip curve is set at the factory.
The UVR drops the breaker on voltage loss — standard for safety disconnects on conveyor or pump feeds. The trip alarm switch gives a separate signal for remote fault annunciation.
Measures 130 mm high, 76.2 mm wide (3-module), 70 mm deep. Front IP40 — fine for enclosed panel mounting; not rated for washdown. Latching endurance is 15,000 cycles — adequate for a feeder breaker that sees infrequent switching.