SENTRON 3VA1220-5MH32-0AA0 — 200 A MCCB with TM120M Release
The 200 A rating holds flat from 40 °C through 50 °C ambient, then derates to 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C — so in a warm panel you lose about 12% of capacity at the top of the operating range. Interrupting capacity is the headline here: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 4.5 kA at 690 V. The 690 V figure of 4.5 kA is more modest, so if your application is a 690 V distribution board, verify the SCCR coordinates with your upstream transformer.