The Siemens SENTRON 3VA1220-5EE42-0AA0 is a 4-pole molded case circuit breaker rated for 200 A continuous current at 40 °C, with a TM220 thermal-magnetic release designed for line protection — meaning it handles overload and short-circuit faults in distribution panels, not motor-starting duty. Its interrupting capacity is what sets it apart: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V. The continuous current holds flat at 200 A from 40 °C through 50 °C, then derates to 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C. Maximum power loss is 42 W, which matters for thermal management inside a sealed enclosure.
Siemens 3VA1220-5EE42-0AA0 SENTRON MCCB, 200 A, 4-Pole, 187
Siemens SENTRON 3VA1220-5EE42-0AA0, molded case circuit breaker, 4-pole, 200 A rated current, TM220 release, line protection, interrupting ratings from 187 kA at 240 V down to 17 kA at 690 V.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Product version | Line protection |
| Parameter | Value |
|---|---|
| Number of poles | 4 |
| Rated operational voltage Ue (AC) | 690 V |
| Current at 40 °C | 200 A |
| Current at 45 °C | 200 A |
| Current at 50 °C | 200 A |
| Current at 55 °C | 194 A |
| Current at 60 °C | 188 A |
| Current at 65 °C | 182 A |
| Current at 70 °C | 176 A |
| Switching capacity class | M |
| Breaking capacity at 240 V | 187 kA |
| Breaking capacity at 415 V | 121 kA |
| Breaking capacity at 440 V | 75.6 kA |
| Breaking capacity at 500 V | 30 kA |
| Breaking capacity at 690 V | 17 kA |
| Power loss, max. | 42 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | TM220 |
| Overcurrent protection function | LI |
| Ground-fault monitoring | Without |
| Parameter | Value |
|---|---|
| Main circuit connection type | nut keeper kit on both ends |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | No |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 0 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Height | 158 mm |
| Width | 140 mm |
| Depth | 70 mm |
| Height (in) | 6.22 in |
| Width (in) | 5.51 in |
| Depth (in) | 2.76 in |
Product details
Frequently asked questions
Where can I buy 3VA1220-5EE42-0AA0 and get a price?
This part is sourced through independent distribution and quoted to order against an RFQ. Submit a request for current availability and pricing — confirmed at quote time.
What is the interrupting capacity of 3VA1220-5EE42-0AA0 at 415 V?
At 415 V the interrupting rating is 121 kA. At 240 V it reaches 187 kA, and at 690 V it is 17 kA.
What type of overcurrent release does 3VA1220-5EE42-0AA0 use?
It uses a TM220 thermal-magnetic release, designed for line protection — not suitable for motor-starting duty where a magnetic-only or electronic release would be required.