Skip to main content
Siemens 3VA1220-6EF32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1220-6EF32-0AH0 SENTRON MCCB, 200A 3-Pole, 220kA

MPN3VA1220-6EF32-0AH0

Siemens SENTRON 3VA1220-6EF32-0AH0, molded case circuit breaker, 3-pole, 200 A at 40 °C, TM240 thermal-magnetic release, 220 kA interrupting at 240 V, line protection design.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1220-6EF32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA12206EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1220-6EF32-0AH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V30 kA
Breaking capacity at 690 V17 kA
Power loss, max.42 W
3VA1220-6EF32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1220-6EF32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1220-6EF32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1220-6EF32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1220-6EF32-0AH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width105 mm
Depth70 mm
Height (in)6.22 in
Width (in)4.13 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1220-6EF32-0AH0 is a 3-pole molded case circuit breaker rated for 200 A continuous at 40 °C, with a TM240 thermal-magnetic overcurrent release. It carries a 220 kA interrupting capacity at 240 V — that rating drops to 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V, so the available fault current at the panelboard determines which voltage column governs your SCCR calculation.

Continuous current holds at 200 A from 40 °C through 50 °C, then derates to 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C. Maximum power loss is 42 W at rated current — that heat stays inside the panel, so factor it into the enclosure thermal budget alongside the other gear in the same compartment.

Auxiliary switching and trip indication

The trip alarm switch changes state only on a fault trip, not on manual open — useful for remote fault annunciation or a shunt-trip interlock.

Environmental and insulation ratings

The 70 mm depth, 105 mm width, and 158 mm height match the standard SENTRON 3VA mounting footprint — it bolts into the same panel cutout as other 3VA frame-size breakers.

Frequently asked questions

Where can I buy 3VA1220-6EF32-0AH0 and get a price?

This part is sourced through independent distribution channels. Submit an RFQ — availability and current pricing are confirmed at quote time.

What is the interrupting rating of 3VA1220-6EF32-0AH0 at 240 V?

220 kA at 240 V. The rating decreases at higher voltages: 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V.

What overcurrent release does 3VA1220-6EF32-0AH0 use?

A TM240 thermal-magnetic release. It is a fixed-trip unit — no interchangeable rating plugs on this variant.

MPN
3VA1220-6EF32-0AH0