Skip to main content
Siemens 3VA1463-5EF32-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1463-5EF32-0BH0 SENTRON MCCB, 630 A, 3-Pole, 187

MPN3VA1463-5EF32-0BH0

Siemens SENTRON 3VA series, molded case circuit breaker, 3VA1463-5EF32-0BH0, 3-pole, 630 A at 40 °C, 187 kA breaking capacity at 240 V, line protection design.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1463-5EF32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA14635EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1463-5EF32-0BH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C630 A
Current at 50 °C630 A
Current at 55 °C618 A
Current at 60 °C607 A
Current at 65 °C595 A
Current at 70 °C583 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.195.4 W
3VA1463-5EF32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1463-5EF32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1463-5EF32-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1463-5EF32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1463-5EF32-0BH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

The Siemens 3VA1463-5EF32-0BH0 is a SENTRON molded case circuit breaker built for line protection duty — 3-pole, rated a full 630 A at 40 °C ambient, and carrying a 187 kA interrupting rating at 240 V. That kind of breaking capacity means it'll clear a hard fault without the arc flash propagating upstream, which is what you want when you're coordinating a main or feeder in a distribution panel.

If your enclosure runs hot, you'll want to check the thermal curve against your actual load rather than just the nameplate. Breaking capacity drops as voltage climbs: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 11.9 kA at 690 V.

Mounting and fit

The breaker measures 248 mm tall, 138 mm wide, and 110 mm deep. The storage range is wider because the breaker isn't dissipating heat when it's sitting on a shelf. If you're commissioning in a cold plant, the -25 °C lower limit is fine for most indoor industrial environments.

The base switch assembly is order code 3VA14635EF320AA0. If you're BOM-freezing a panel design, note that the auxiliary switch config (2 aux + 1 trip alarm) and the UVR are factory-integrated — you're not adding those in the field on this variant.

Frequently asked questions

What is the breaking capacity of this MCCB at 240 V?

187 kA at 240 V. At 415 V and 440 V it's 121 kA, at 500 V it's 75.6 kA, and at 690 V it's 11.9 kA.

Where can I buy 3VA1463-5EF32-0BH0?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

Does this breaker include an undervoltage release?

Yes, it's fitted with an undervoltage release (UVR) as standard, plus two auxiliary switches and one trip alarm switch.

MPN
3VA1463-5EF32-0BH0