Skip to main content
Siemens 3VA1463-7EE42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1463-7EE42-0AA0 SENTRON MCCB, 630 A, 4-Pole, TM22

MPN3VA1463-7EE42-0AA0

Siemens SENTRON 3VA1463-7EE42-0AA0, molded case circuit breaker, 4-pole, 630 A at 40 °C, TM220 release, 440 kA breaking capacity at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1463-7EE42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1463-7EE42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C630 A
Current at 50 °C630 A
Current at 55 °C618 A
Current at 60 °C607 A
Current at 65 °C595 A
Current at 70 °C583 A
Switching capacity classC
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V154 kA
Breaking capacity at 690 V17 kA
Power loss, max.192.9 W
3VA1463-7EE42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1463-7EE42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1463-7EE42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1463-7EE42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1463-7EE42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.76 in
Width (in)7.24 in
Depth (in)4.33 in

Product details

Siemens SENTRON 3VA1463-7EE42-0AA0 — 630 A MCCB, 4-Pole, TM220 Release

Breaking capacity reaches 440 kA at 240 V, 242 kA at 415 V, and 154 kA at 500 V, dropping to 17 kA at 690 V — numbers that tell you this breaker is built for high-available-fault-current installations, typically close to a transformer or in a main switchboard. The 630 A continuous rating holds flat from 40 °C to 50 °C, then derates to 583 A at 70 °C; if your panel ambient runs hot, that derating curve (–) is the one to use for sizing.

The breaker measures 184 mm wide, 248 mm high, and 110 mm deep — a 4-pole frame that fits standard Siemens SENTRON mounting bases and switchboard cubicles. Front IP40 protection means it is suited for indoor panel installation where dust ingress is limited; no washdown or outdoor rating is claimed. No communication function or voltage trip indicator is built in — this is a plain thermal-magnetic MCCB. For remote trip indication or energy metering, add an external module.

MPN
3VA1463-7EE42-0AA0