Skip to main content
Siemens 3VA1463-7EF42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1463-7EF42-0AA0 SENTRON MCCB, 630 A, 4-Pole, TM24

MPN3VA1463-7EF42-0AA0
Active

Siemens SENTRON 3VA1463-7EF42-0AA0, molded case circuit breaker, 4-pole, 630 A continuous at 40 °C, TM240 thermal-magnetic release, line protection version.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1463-7EF42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1463-7EF42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C630 A
Current at 45 °C630 A
Current at 50 °C630 A
Current at 55 °C618 A
Current at 60 °C607 A
Current at 65 °C595 A
Current at 70 °C583 A
Switching capacity classC
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V154 kA
Breaking capacity at 690 V17 kA
Power loss, max.192.9 W
3VA1463-7EF42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1463-7EF42-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1463-7EF42-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1463-7EF42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1463-7EF42-0AA0 — Mechanical
ParameterValue
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.8 in
Width (in)7.2 in
Depth (in)4.3 in

Product details

The Siemens 3VA1463-7EF42-0AA0 is a 4-pole SENTRON molded case circuit breaker rated for 630 A continuous at 40 °C, with no derating needed until 55 °C where it still holds 618 A. That means it carries full rated current in most ventilated enclosures without forced cooling — the thermal curve is flat across the typical panel ambient range. Breaking capacity hits 440 kA at 240 V, 242 kA at 415 V, and still 17 kA at 690 V, so it handles high-fault utility feeds without cascading upstream.

Sizing and selectivity notes

At 630 A frame size with a 4-pole footprint (248 mm height, 184 mm width, 110 mm depth), this breaker fits standard SENTRON mounting patterns. The IP40 front protection means it's suitable for indoor switchboards but not washdown zones.

Panel integration

The motor drive option (listed as available) allows remote trip and reset for automated lines. No communication module onboard — this is a standalone breaker, not a networked power distribution unit.

Frequently asked questions

Where can I buy 3VA1463-7EF42-0AA0 and how do I get a price?

This part is quoted to order against an RFQ. Availability and current pricing are confirmed at quote time through our sourcing desk — submit an RFQ for a firm commercial response.

What are the key ratings for this MCCB?

630 A continuous at 40 °C, 4-pole, TM240 thermal-magnetic release, breaking capacity of 440 kA at 240 V, 242 kA at 415 V, and 17 kA at 690 V. Rated insulation voltage is 800 V.

What compliance documentation does this brand provide for 3VA1463-7EF42-0AA0?

As a Siemens SENTRON product, it carries the standard IEC/UL certifications expected for molded case circuit breakers. Specific RoHS, REACH, and UL documentation is available upon request with the RFQ.

MPN
3VA1463-7EF42-0AA0