SENTRON 3VA2 — 40 A line protection MCCB with ETU320
Breaking capacity is 440 kA at 240 V AC, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V — figures that place it well into the high-interrupting category for industrial service-entrance or sub-distribution boards where fault currents are substantial.
The breaker has no undervoltage release, no voltage trigger, and no communication function — it is a pure line-protection device. Ground-fault monitoring is not integrated; if GF protection is needed, pair it with an external module or specify a different variant.
ETU320 trip unit — what it means for coordination
The ETU320 is an electronic trip unit with adjustable overload (Ir) and short-circuit (Isd, Ii) thresholds, plus a time-delay setting for short-delay (tsd). That adjustability lets the site electrical engineer tune selectivity with downstream breakers without swapping trip packs — a practical advantage over fixed thermal-magnetic units when the load profile or fault-current study changes after commissioning.